| UPS type |
Line Interactive UPS corrects brownout and overvoltage conditions, plus offers battery support for blackouts and severe voltage fluctuations. Includes LAN port, bundled software, 'surge only' outlets and modem line surge suppression. |
| Input/output voltage |
120 |
| Input/output frequency (Hz) |
60 |
| Ouput VA |
500 |
| Output watts |
300 |
| On-line waveform |
Pure Sine |
| On battery waveform |
PWM Sinusoidal |
| Voltage regulation |
Line interactive system corrects voltage to nominal levels, boosting input between 75 to 112 volts and reducing input between 127 and 147 volts. Output voltage in battery mode is regulated to 120 volts +/- 5%. |
| Full load runtime (min.) |
5 |
| 1/2 load runtime (min.) |
17 |
| Typical runtime (PC w/15" mon.) |
up to 30 min. |
| External battery compatible |
Not supported. See selected Smart XL, RM and Datacenter models for this capability. |
| Recharge rate to 90% (hours) |
2-4 |
| Transfer time (milliseconds.) |
2-4 |
| Suppression joule rating |
360 |
| Maximum surge current (amps) |
27,000 |
| Suppression response time |
Less than one nanosecond |
| EMI/RFI noise reduction |
Greater than 40 dB @ 1 MHz |
| High volt switch to battery |
147 |
| Low volt switch to battery |
75 |
| UPS supported outlet type / qty. |
3 NEMA 5-15R |
| "Surge only" outlet type / qty. |
3 NEMA 5-15R |
| Cord length |
6.00 ft. / 1.83 m |
| Plug type |
NEMA 5-15P |
| Dimensions HxWxD (inches) |
8.25 x 4.75 x 7 |
| Shipping weight |
15.50 lbs. / 7.03 kg |
| Fax/modem surge protection |
Set of RJ11 jacks protects a single phone line |
| Network interface port |
Built in DB9 standard communications port for use with PowerAlert software and cabling. |
| Software & cable included |
Includes cable and PowerAlert software. |
| Product warranty (yr.) |
2 |
| Connected equipment warranty |
Ultimate Lifetime Insurance protects connected equipment from damage due to surges up to $50,000 (USA & Canada only). |
| Battery access |
Battery Door |
| Controls, indicators and additional
features |
On/off and Self test/alarm silence switches, LEDs indicate on-line,on-battery, voltage correction, and battery low/replace, audible alarms. 3 UPS supported and 3 Surge protected outlets. |
| |
|
| |
|
| Ingram Micro |
519270 |
| TechData |
880946 |
| D&H |
OMNISMART500PNP |
|